Powerful solution delivers exceptional cooling capacity and unparalleled reliability, empowering you to operate efficiently and sustainably.
This is the revolutionary DCX 1MW Immersion Optimized DryCooler, designed to conquer the most demanding heat transfer challenges faced by large-scale immersion farms. This powerful solution delivers exceptional cooling capacity and unparalleled reliability, empowering you to operate efficiently and sustainably. Delivers 1MW of heat rejection in 35°C (95°F) ambient air temperature, ensuring optimal cooling performance for even the most densely packed immersion racks. This compact design saves space and allows for flexible placement within your data center. Rugged and reliable construction withstands harsh environments, including low temperatures, heavy snow, strong winds, high humidity, and more. Durable coating protects the unit from corrosion and ensures long-lasting performance. Minimum footprint saves valuable space within your data center. 20ft container sized for 1.2MW capacity enables efficient space usage. Air-based cooling eliminates the need for water, reducing your environmental footprint. High-quality fans and controllers ensure efficient operation and minimize energy consumption. Choose from EU-produced or US-made units to suit your specific needs.
Application
Immersion od Direct Chip cooling systems heat rejection
Cooling capacity
(Ambient temp=35°C)
1 Megawatt
Dimensions
7000(W) x 2620(D) x 2300(H) mm
Fans
12 x 800 mm
Max power consumption
32.4 kW
Power Standard
400V/3Ph/50hz
Fittings
4" / DN100
Fluid temperature In / Out
60 / 40 °C
Nominal volume flow
26.9 mᶾ/hf
Pressure drop
0.35 bar
Designed to handle medium and large-scale deployments while occupying no more than a single square meter per system. It is the ultimate solution for mining farms and high-density data centers looking to boost productivity and reduce costs.
Would you like to order a specific product, or maybe you have an entire project at hand? In order to provide you with the best experience possible, we kindly ask you to include the following infromation in your message: